BCIN House 2024 Exam - Min. Glazing Requirements (OBC Part 9)
- Vijaykumar Patel

- 4 days ago
- 6 min read
Minimum Window Areas for Residential Occupancy – Bathrooms, Bedrooms & More
Understanding Part 9 glazing requirements is essential for anyone preparing for the BCIN House Exam or working on residential permit drawings in Ontario.
One of the most commonly tested sections is OBC 9.7.2.3 – Minimum Window Areas, especially when questions involve bathrooms, basements, and second suites.
This blog breaks it down in plain language, ties it to real exam questions, and shows how it applies on actual projects.
Why OBC 9.7.2.3 Matters
The Ontario Building Code requires minimum natural light in residential rooms to support:
Health & safety
Habitability
Code-compliant design

However, artificial lighting changes the rules, and this is where many BCIN candidates get tripped up.
Key Code Reference
OBC 9.7.2.3 – Minimum Window Areas
Understanding Table 9.7.2.3
Table 9.7.2.3 provides two compliance paths:
Option 1 – No Electrical Lighting
A Larger window area is required to ensure adequate natural light.
Option 2 – With Electrical Lighting
Window requirements are reduced or eliminated because artificial light is provided.

👉 Most modern homes fall under “with electrical lighting.”
Bathroom Window Example (BCIN Exam Style)
Question
A bathroom window is located 900 mm above the finished floor and has an area of 1.2 m². What are the glazing requirements according to OBC 9.7.2.3?
Answer Choices
A) 5% of floor area
B) 0.37 m²
C) 5% of floor area
D) Not required due to artificial lighting
✅ Correct Answer
D) Not required due to artificial lighting
Why Answer D Is Correct
According to Table 9.7.2.3, for a water closet room (bathroom):
Condition | Requirement |
No electrical lighting | 0.37 m² minimum glazing |
With electrical lighting | Windows not required |
Since modern bathrooms are assumed to have electrical lighting, the Code does not require any minimum window area.
👉 The 900 mm sill height and 1.2 m² window size are irrelevant once electrical lighting is provided.
Extract from Table 9.7.2.3 (Simplified)
Room Type | No Electrical Lighting | With Electrical Lighting |
Laundry / unfinished basement | 4% of area | Windows not required |
Water closet room (bathroom) | 0.37 m² | Windows not required |
Kitchen | 10% of area | Windows not required |
Living / dining rooms | 10% | 10% |
Bedrooms | 5% | 5% |
Why the Code Allows This
The intent of 9.7.2.3 is adequate illumination, not daylight at all costs.
Artificial lighting provides consistent illumination
Bathrooms are short-duration occupancy spaces
Mechanical ventilation handles moisture (not windows)
Second Suite & Basement Bathroom Example
This is where many designers struggle 👇
Scenario
You’re designing a basement second suite with:
A bathroom below grade
Limited exterior wall exposure
No practical window location

Solution
✔ Provide electrical lighting
✔ Meet ventilation requirements under Part 9
✔ No glazing required under 9.7.2.3
This is perfectly code-compliant and commonly approved by municipalities.
Common BCIN Exam Mistakes
❌ Automatically choosing 0.37 m² for bathrooms
❌ Ignoring the “with electrical lighting” column
❌ Confusing habitable rooms with service rooms
❌ Overthinking window sill height (not relevant here)
💡 Exam Tip: If the question mentions electrical lighting, always check Column 3 first.
Important Notes from Table 9.7.2.3
Doors & skylights count as windows
Combined rooms follow the most restrictive requirement
Bedrooms also trigger egress rules under 9.9.10
Live/work units may fall under Part 3 requirements
Why This Knowledge Is Essential
For BCIN House candidates, this topic:
Appears frequently on exams
Affects permit approval
Impacts the basement and second suite design
Prevents unnecessary design changes and client costs
Part 11 Allowance for Existing Houses (C110) – 50% Glazing Reduction Explained
When working on older houses, designers often have more flexibility than they realize. The Ontario Building Code recognizes this through Part 11 – Renovations, specifically Compliance Alternative C110.
This provision is especially helpful for basement renovations and second suites, where meeting full Part 9 glazing requirements can be difficult due to tight property lines or spatial constraints that limit the amount of glazing that can be provided.
When Can Part 11 Be Used?
✔ The house is more than 5 years old
✔ The work is a renovation or change of use
✔ You are not creating new structural conditions requiring full Part 9 compliance
In these cases, a designer may apply Part 11 instead of the strict Part 9 rules.

Key Reference
Part 11 – Compliance Alternative C110 (Page 46)
Where windows are not used as a means of egress and where they do not conflict with ventilation requirements, the minimum glass area shown in Table 9.7.2.3 may be reduced by 50%.
What This Means in Simple Terms
If:
A window is NOT required for egress, and
Ventilation requirements are satisfied by mechanical ventilation,
👉 Then the minimum glazing area from Table 9.7.2.3 can be reduced by 50%.
This is a code-approved relaxation, not a workaround.
Simple Second Suite Example
Existing Condition
House built in 2008 (older than 5 years)
Basement converted into a second suite
Bedroom floor area = 12 m²
Part 9 Requirement
Bedroom glazing = 5% of floor area
12 m² × 5% = 0.60 m²
Using Part 11 (C110)
Window not used for egress
The bedroom has hard-wired electrical lighting
Mechanical ventilation provided
✔ Allowed reduction = 50%
👉 Revised minimum glazing:0.60 m² × 50% = 0.30 m²
✅ Compliant under Part 11
Why This Is Critical for Basement Suites
Basement second suites often face:
Shallow window wells
Existing foundation limitations
Property line setbacks
Part 11 C110 acknowledges reality and allows designers to work with existing conditions safely.
Important Limitations
❗ This reduction cannot be used if:
The window is required for egress
Ventilation requirements are not met
Life safety is compromised
Always verify:
Egress under 9.9.10
Ventilation under Part 9
“May” vs “Shall” – BCIN Exam Gold
Understanding these two words is essential for the BCIN House exam.
Shall
Mandatory
No discretion
Must be followed

Example:
Minimum window glass area shall conform to Table 9.7.2.3.
May
Permitted
Optional
Designer discretion
Example from C110:
The minimum glass area may be reduced by 50%.
👉 This means:
The designer is allowed to apply the reduction
It is not mandatory
The Authority Having Jurisdiction (AHJ) may still review applicability
Common Designer Mistakes
❌ Applying the 50% reduction to egress windows
❌ Using Part 11 for new construction
❌ Forgetting mechanical ventilation
❌ Assuming “may” means “must be accepted”.
BCIN Exam Tip
If a question says:
Existing house
Renovation
Part 11 applies
👉 Always look for relaxations like C110.
Final Takeaway
OBC 9.7.2.3 – Minimum Window Areas is one of the most important glazing provisions under Part 9, and a frequent focus on the BCIN House Exam. The key to mastering this section is understanding that the Code is concerned with adequate illumination, not simply the presence of windows.
Designers who understand:
when windows are required,
when they are not required, and
when reductions are permitted,
can design smarter, avoid unnecessary construction, and navigate both permit reviews and BCIN exam questions with confidence.
FAQ
Are windows required in bathrooms under the Ontario Building Code?
No. Under OBC 9.7.2.3, bathroom (water closet room) windows are not required when electrical lighting is provided. A minimum glazing area of 0.37 m² only applies when no electrical lighting is installed.
Does window height or sill elevation affect glazing requirements?
No. Sill height does not impact minimum glazing area under 9.7.2.3. Only the presence of electrical lighting and the room type determine the requirement.
Can a basement bathroom in a second suite have no window?
Yes. A basement bathroom may have no window provided:
Electrical lighting is installed, and
Ventilation requirements under Part 9 are met
This is fully code-compliant and commonly approved by municipalities.
When does the 0.37 m² bathroom window requirement apply?
The 0.37 m² minimum glazing applies only when a bathroom has no electrical lighting. This typically affects:
Seasonal dwellings
Off-grid buildings
Older structures without permanent lighting
Do bedrooms always require windows?
Yes. Bedrooms must comply with:
Minimum glazing area under 9.7.2.3, and
Egress requirements under 9.9.10
Even when Part 11 applies, egress requirements cannot be reduced.
Can Part 11 reduce glazing requirements in older houses?
Yes. For houses older than 5 years, Part 11 – Compliance Alternative C110 allows the minimum glazing area from Table 9.7.2.3 to be reduced by 50%, provided:
The window is not used for egress, and
Ventilation requirements are met
Can doors or skylights count toward required glazing area?
Yes. Under the notes to Table 9.7.2.3, the unobstructed glass area of a door or skylight is considered equivalent to a window.
What is the most common BCIN House exam mistake related to glazing?
The most common mistakes include:
Automatically selecting 0.37 m² for bathrooms
Ignoring the “with electrical lighting” column
Applying Part 11 reductions to new construction
Assuming “may” means “must be accepted.”
How should I approach glazing questions on the BCIN House exam?
Follow this order:
Identify the room type
Check if electrical lighting is provided
Confirm if Part 9 or Part 11 applies
Verify egress and ventilation requirements (only if using part 11)
If you found this question helpful, we have hundreds of practice questions on our portal, including real exam-style scenarios, image-based questions, and challenging problems designed to help you pass the BCIN House 2024 Exam on your first attempt.
*Please note that the information shared in our blog is for educational purposes only, and we do not assume any liability for the actions or decisions made based on this information.



Comments